Application :
    • Predominantly used for primary underground distribution
    • Suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight
    • To be used at 35,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation
Standards :
    35kV Primary UD Cable meets or exceeds the following ASTM specifications:
    • B 230: Aluminum 1350-H19 Wire for Electrical Purposes
    • B 231: Aluminum 1350 Conductors, Concentric-Lay-Stranded
    • B 609: Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
Construction :
    • The phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy
    • Cable is composed of the conductor with moisture block in the strands, covered by a semi-conducting cross-linked polyethylene strand shield, a tree-retardant cross-linked polyethylene primary insulation, and a semi-conducting cross-linked polyethylene insulation shield
    • Conductors are available with either 100% or 133% insulation levels
    • Concentric neutral of bare copper wires and an insulating polyethylene jacket is applied over the insulation shield
    • Cable identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket
Description